Tomzn TOQ7 125A 4P AC Automatic Transfer Switch (ATS)
Product Overview
The Tomzn TOQ7 125A 4P Automatic Transfer Switch (ATS) is designed to automatically transfer an electrical load between two compatible power sources. It helps maintain power availability when the primary supply becomes unavailable or falls outside the acceptable operating conditions.
An Automatic Transfer Switch is commonly used in electrical systems that have a primary power supply and a backup source, such as a utility supply and a compatible inverter or generator arrangement. Instead of requiring manual operation every time the primary source fails, an ATS monitors the power sources and performs the transfer according to its control logic.
The Tomzn TOQ7 features a 125A rated current and a four-pole configuration. It is designed for compatible three-phase distribution arrangements with neutral and uses a control supply of approximately 220–240V AC, depending on the selected variant.
Its compact modular design supports 35mm DIN rail mounting, making it suitable for compatible distribution panels and electrical enclosures.
Key Features
- Brand: TOMZN
- Model: TOQ7
- Product Type: Automatic Transfer Switch (ATS)
- Rated Current: 125A
- Pole Configuration: 4 Pole (4P)
- Control Supply: AC 220–240V
- Frequency: 50/60Hz
- Switching Time: Less than 50ms (manufacturer-listed)
- Rated Insulation Voltage: AC 690V
- Rated Impulse Withstand Voltage: 8kV
- Mounting: 35mm DIN rail
- Operation: Automatic and manual switching, depending on version
- Application: Compatible dual-source AC power systems
Automatic Power Source Switching
The main purpose of the Tomzn TOQ7 ATS is to transfer a connected electrical load between two power sources.
In a typical dual-source installation, one supply is selected as the primary source while the second is configured as the backup supply.
When the primary source becomes abnormal or unavailable, the ATS detects the condition and transfers the load to the backup source according to its operating logic. When the preferred source returns to acceptable conditions, the device can transfer the load back according to its configured operating mode.
This automatic operation reduces the need for manual source selection and helps improve power availability for connected equipment.
The actual transfer sequence depends on the ATS model, source arrangement, and manufacturer instructions.
125A Rated Current Capacity
The Tomzn TOQ7 is available in a 125A current rating for installations that require a higher-capacity automatic transfer switch.
The 125A rating must be matched with the connected load, cable capacity, upstream protection, and electrical installation design.
Before selecting an ATS, the installer should consider:
- Total connected load current.
- Maximum expected operating current.
- Starting current of motors and other equipment.
- Source voltage and frequency.
- Required pole configuration.
- Suitable upstream and downstream protection.
A 125A rating does not mean the device can safely handle every load up to 125A under all conditions. The manufacturer’s rated operating conditions and utilization category must also be considered.
Four-Pole Configuration
The Tomzn TOQ7 4P ATS features four switching poles. This arrangement is commonly used in compatible three-phase, four-wire systems.
In a typical three-phase installation, the four poles are used for the three phase conductors and neutral according to the manufacturer’s connection diagram.
The four-pole arrangement helps coordinate the transfer of the designated conductors between the two power sources.
Correct wiring is essential to prevent improper source connections and unwanted electrical interactions. The neutral arrangement and switching sequence must follow the manufacturer’s instructions and applicable electrical regulations.
Fast Switching Performance
The TOQ7 series is advertised with a switching time of less than 50 milliseconds.
Fast transfer helps reduce the duration of power interruption when changing between compatible sources. This can be useful in installations where maintaining power availability is important.
However, a transfer time below 50ms does not mean that the device provides a completely uninterrupted or zero-break power supply. Sensitive equipment may still require a UPS or another suitable power-conditioning solution.
Actual switching performance depends on the source conditions, operating mode, and installation configuration.
Suitable Applications
The Tomzn TOQ7 125A 4P ATS may be considered for compatible applications such as:
- Three-phase electrical distribution panels.
- Compatible solar inverter and utility power arrangements.
- Backup power distribution systems.
- Commercial buildings.
- Shops and offices.
- Compatible generator or alternative-source installations.
- Electrical systems requiring automatic dual-source transfer.
Source compatibility is important: TOMZN’s product information describes specific PV inverter and utility-source arrangements and provides connection instructions for the primary and backup inputs. Do not assume every TOQ7 variant supports every combination of grid, generator, and inverter sources. Confirm the intended source arrangement with the manufacturer’s documentation before purchase and installation.
Technical Specifications
| Specification | Details |
|---|---|
| Brand | TOMZN |
| Model | TOQ7 |
| Product Type | Automatic Transfer Switch |
| Rated Current | 125A |
| Pole Configuration | 4P |
| Rated Working Voltage | AC 400V system, subject to configuration |
| Control Supply | AC 220–240V |
| Frequency | 50/60Hz |
| Rated Insulation Voltage | AC 690V |
| Impulse Withstand Voltage | 8kV |
| Switching Time | Less than 50ms |
| Electrical Life | 2,000 operations |
| Mechanical Life | 5,000 operations |
| Mounting | 35mm DIN rail |
| Classification | PC Class |
Technical note: The TOQ7 is a PC-class automatic transfer switch. It is intended for power-source transfer and should not be treated as a complete overload and short-circuit protection device. Appropriate protective devices must be installed according to the system design. The control supply and actual source-voltage requirements should be confirmed from the supplied model’s label and wiring diagram.
DIN Rail Installation
The Tomzn TOQ7 is designed for installation on a standard 35mm DIN rail.
This modular mounting arrangement makes it suitable for compatible electrical distribution boards and control enclosures.
DIN rail mounting provides several practical benefits:
- Convenient installation in compatible electrical panels.
- Organized wiring and distribution arrangements.
- Easier integration with other electrical control equipment.
- A compact installation arrangement.
- Convenient access for inspection and maintenance.
The installer should ensure that the enclosure has adequate space for the ATS and connected wiring. Proper cable routing and terminal connections are essential for reliable operation.
Automatic and Manual Operation
The TOQ7 series is designed for automatic transfer between two power sources. Depending on the selected model and operating arrangement, manual switching may also be available.
Automatic operation allows the device to monitor the designated supply conditions and transfer the load when required.
Manual operation can be useful during testing, maintenance, or situations where an operator needs to select a source according to the manufacturer’s instructions.
Always check the actual model’s operating controls and manual override procedure before installation.
Benefits of Using an Automatic Transfer Switch
An ATS provides an organized way to manage two electrical power sources.
The Tomzn TOQ7 offers several practical advantages:
Automatic Source Selection
It reduces the need for manual intervention when the preferred power source becomes unavailable.
Dual Power Supply Arrangement
It allows a compatible electrical installation to use a primary source and a backup source.
Four-Pole Switching
Its 4P arrangement supports compatible three-phase and neutral switching configurations.
Fast Transfer
The manufacturer lists a transfer time of less than 50ms under specified conditions.
Modular Installation
The 35mm DIN rail mounting design supports integration into compatible electrical distribution panels.
Installation and Safety Guidelines
The Tomzn TOQ7 125A ATS must be installed by a qualified electrician familiar with three-phase power distribution and automatic transfer systems.
Before installation, check the following:
- Confirm the model is TOQ7 125A 4P.
- Verify the rated current and operating voltage.
- Confirm the control supply requirements.
- Identify the primary and backup source terminals.
- Follow the manufacturer’s wiring diagram.
- Confirm the neutral switching arrangement.
- Check the compatibility of both power sources.
- Install suitable upstream and downstream protective devices.
- Use cables and terminals rated for the intended current.
- Tighten all connections according to the manufacturer’s instructions.
- Secure the ATS on a compatible 35mm DIN rail.
Always isolate both power sources before installation or maintenance. An ATS can have more than one energized input, so disconnecting only the primary supply may not make the equipment safe to work on.
Important Protection Information
An automatic transfer switch and a circuit breaker perform different functions.
The ATS transfers a connected load between compatible power sources. A circuit breaker or fuse provides the required protection against overloads and short circuits.
The TOQ7 is a PC-class ATS and should not be relied upon as a replacement for suitable circuit protection. Install appropriately rated protective equipment according to the manufacturer’s recommendations and local electrical standards.
The device should also be selected according to its rated operating current and utilization category. Motor loads, inductive loads, and other demanding applications may require additional consideration.
Buy Tomzn TOQ7 125A 4P Automatic Transfer Switch
Choose the Tomzn TOQ7 125A 4P Automatic Transfer Switch for compatible dual-source AC power systems that require automatic switching between primary and backup supplies.
Its four-pole configuration, 125A rated current, fast transfer operation, and DIN rail mounting make it a practical option for suitable three-phase electrical distribution arrangements.
Before ordering, confirm the exact source compatibility, control voltage, and wiring configuration required for your installation. Correct selection and professional installation help ensure dependable power transfer and safe operation.



Reviews
There are no reviews yet.